image image image image image
For indoor environment Compact water chiller for indoor environment. Ambient air is heated by the surrounding environment. Therefore, if the chiller is placed in a small and low room, it must be drained out by the air conduits.    
For outdoor environment JN-xx coolers are compact for external environment. In winter, the water must be discharged or used antifreeze. Galvanized frame, galvanized sheet metal powder coated for outdoor use, or stainless steel finish.    
Split systems Chiller with separate condenser. Refrigeration unit is located inside and condenser is in the outside. All the heat is discharged into the environment.      
Special applications The chillers are compact for outdoor use. It is necessary to drain the water in winter or use antifreeze. Fire-galvanized frame, galvanized sheets, powder colour to the outside, or stainless steel.    
Accessories Accessories.
Chiller J-50 capacity 50 kW

Chiller J-50 - source of cold water, air cooled

The J-50 chiller is a compact chiller for indoor environment. It contains a cooling circuit with appropriate protections, one semi-hermetic compressor, air cooled condenser with fans, regulation, water tank with evaporator, pump with bypass, electrical switchboard, digital temperature controller, fault showing. The chiller heats the ambient air, in lower spaces it is necessary to vent the heated air through the discharge air duct. In the winter months, the chiller can heat space. If the room is air-conditioned at the working place of the chiller, in the summer months we recommend sucking the air through the suction duct from outside.

 

TECHNICAL PARAMETERS

Cooling capacity: 50 kW at water temperature 13 °C
Input power: 16.7 kW
Current: 46.0 A
Starting current: 96.0 A
Voltage: 3+N+PE~50Hz 400/230V TN-S
Circuit breaker: motor circuit breaker 50 A
Supply cable: CYKY-J 5x10
Refrigerant / volume: R 407C / 16.0 kg
Tank volume: 500 l
Liquid flow / pressure 150 l/min / 3.0 bar
Air flow: 14,000 m3/h
Weight: 770 kg
Coverage: IP 43

 

Flow of used pumps: Cooling capacity:


Heating capacity: